Enquiry No. : 6081790 Theqer (Iraq)
Description :We are company for supplier, we need this transformer
GST : Out door Transformer
IES 76 load Top _ Changing Transformer
1) Rated power
32MVA 1.HV
16MVA 2.LV1
16MVA 3.LV2
2)Number of phases : 3
3)Rated frequency : 50 HZ
4)Rated Voltage
132 kv 1.HV
6.3 kv 2.LV1
6.3 kv 3.LV2
5)Rated current
140 A 1.HV
1470A 2.LV1
1470A 3.LV2
6)Insulation level
140 KV R.M.S 550 KV PEAK 1.HV
140 KV R.M.S 325 KV PEAK 2.HV NEUTRAL
22 KV R.M.S 60 KV PEAK 3.LV1
22 KV R.M.S 60 KV PEAK 4.LV2
7)Type of cooling : ONAN
8)Ambient temperature (- 10 C TO + 55 C)
9)Total mass : 69 Ton
10)Oil mass : 29 Ton
11)Oil Quantity of main tank 18800 litter
12) Oil Quantity of deviator switch 120 litter
13) Voltage impedance at 75 C 32 MVA
9-7% HV LV1
22-7% LV1 LV2
8.8% LV2 HV
14)Connection Y N /D11 /D11
15)Origin :