Enquiry No. : 8080933 Karachi (Pakistan)
Description :Subject: Finned water tubes for re-tubing of hydrogen
coolers of generators,
Dear Sir,
With reference to the above, we would like to introduce our selves as
one of the leading suppliers of Mechanical items to utility company in
Pakistan. One of our regular customer which is an electric utility has
requirement for the subject mentioned items. We request you to kindly
quote your best FOB & CNF Karachi prices valid for 90 days Your
offer should be supported by technical literature / catalogs.
S.No Description QTY
01. Tube H2 400 #s.
Cooler, ID=15 mm, OD= 19 mm, L= 4000 mm
Finned water tubes for re-tubing of hydrogen Coolers of generators
Tube material: jis stba-12 equivalent to ASTM A-209 t1
(seamless carbon mo steel alloy)
Temperature limit: 260 deg c
Length of tubes: 4000 mm
Bore (inner diameter): 15 mm
Thickness: 2 mm
Outer diameter: 19 mm
Bare length at both ends: 127 mm
Fin material: copper
Thickness of fins: 0.3 to 0.4 mm
Number of fins per inch: 8.5
Outer diameter of fins: 37 mm
Type of fins: KL (knurled-l fin) i.e fin foot is pre-formed into #l# shape
and applied to the base tube under tension. Knurling tools both precede
and follow the laying down of the fin foot so that the fin material is locked
into the pre-knurled tube. If a small portion of fin is removed from the base
tube, the adjacent spiral fins should remain intact on their position i.e they
should not collapse.
Finish: finned tubes completely tinned by electroplating method after fining.
Test To Be Performed:
The following tests should be peformed on each tube at manufacturer works.
I Hydrostatic test at 42 bars
Ii. Eddy current test as per article-8 of ASME section-v and SE-309 of
article-26
III. Material test and dimensional check
Documents to be submitted:
The contractor shall submit the following test reports along with the supply.
I. Material test report
II. Dimensional check report
III. Hydrostatic test report (detailed)
IV. Eddy current test report (detailed)